LIT-PX112
InteliPANEL PDS
Chromalox ® PRECISION HEAT AND CONTROL
A Revolutionary, Intelligent Process Control Panel
The Intelligent Solution for Simplified Configuration and Local Monitoring with Greatly Reduced Setup Time
From the leader in process heat and control comes the Chromalox ® intelliPANEL ™ control panel. The idea behind the Chromalox ® intelliPANEL ™ control panel is to make control measurement, instruments, alarm configuration, control algorithms, start-up, and trouble- shooting easy. At the same time, the intelliPanel ™ control panel provides the widest array of diagnostics available today for process-critical heating applications. A Revolutionary Concept in Process Temperature Control
Loaded with Diagnostic Features The Chromalox ® intelliPANEL ™ control panel brings the power of several instruments to your application: The unique touchscreen LCD panel provides simpli- fied configuration settings and local monitoring that greatly reduces setup time compared to DIN-style controllers and conventional PLC systems. It features a graphic user interface and simple programming functions. The Industry's First Process/Power Control with a Color Touchscreen Flat Panel Display
• Voltmeters • Ammeters • Wattmeter • Watt-hour meter • Ground fault monitoring and trending • Man-machine interface • Six pen trend chart • Communications • Resistance monitoring • Temperature alarms • SCR power control • Four selectable control algorithms
Temperature Sensing that Meets Your Application Requirements The intelliPANEL ™ system offers four selectable control algorithms: single loop PID, Delta T (differential), cascade process to sheath, and cas- cade outlet to sheath. These options include selectable manual or auto tuning.
The advanced intelliPANEL ™ design provides standard panel ratings from <100 to 1200 amps with voltage ranges of 208 to 600 Vac, three-phase power. In addition to the IntelliPANEL ™ central control unit, the patented Chromalox ® MaxPac SCR power con- troller, featuring built-in power distribution, selectable single/three-cycle resolution, an electronic heat sink temperature monitoring and warning system, provides uniform heating with Chromalox ® DOT variable-time- base firing to insure increased heater life by reducing thermal shock.
There are five user-selectable temperature ranges: 0˚-250˚, 0˚-500˚, 0˚-1000˚, and 0˚-2000˚. Minimum and maximum setpoints can be established and set point ramping is configurable.
The intelliPANEL ™ system has the ability to monitor up to eight temperature inputs for any one of four conditions; Hi/Hi, Hi, Lo, and Lo/Lo alarms. Additionally, each alarm can be programmed as either latching or non-latching, and can be The "Smart" intelliPANEL ™ Display Makes Configuring, Monitoring, and Maintenance Easy
Time- and Money-Saving Features and Benefits at a Glance Quick installation • Built-in help screens and Startup • Push-button programming • Quick learning curve • Auto-tune feature • System master screen automatically reminds operator of error conditions and panel status
mapped to any or all of the four alarm outputs. All inteIIiPANEL ™ alarms are identi- fied and logged with a time-and-
Lower Operating
• Reduced equipment downtime and less maintenance with SCR control • Longer heater life because Chromalox ® DOT Firing minimizes thermal shock which lessens expansion and contraction • Chromalox ® DOT firing control provides integral on/off cycle times • Allows one common panel and HMI to service hundreds of heat and control applications in your plant
Costs
date stamp, count, and action taken.
High Flexibility
Identifies a Potential • 8 sensor inputs are monitored for Failing Heater diagnos ing and troubleshooting shut- down conditions or excursions • Built-in virtual trend chart for trouble- shooting, tuning, and diagnostics • Ground fault monitoring and trending
A pop-up System Master Screen is automatically dis- played any time a shutdown event occurs within the system. The shut- down conditions
• Heater resistance monitoring • Current unbalance monitoring
• Current and power monitoring via built- in virtual metering: volts, amps, watt-hour, watts, and life factor (eliminates mechanical metering)
are listed on the System Master, and flashing red text indicates the event or events that caused the shutdown.
Flexible, Responsive • Four selectable control modes Control ✔ Single loop ✔ Temperature differential ✔ Two cascade modes
There are ten status indicators for key system elements. These indicators include Alarm Input 1 (or Purge Alarm), Ground Fault, Breaker
• Customer-supplied 4 to 20 mA command signal feature for optimal performance in your process application
Status, Heatsink Overtemperature, and High Limit.
Virtual Alarm Panel • Eliminates need for pilot lamps, panel boards, and flag relays
All eight temperature inputs have text identification fields that allow the user to name the sensors for
The Chromalox intelliPANEL ™ control panel offers four levels of security with user-defined numeric passwords: Manager, Engineer, Supervisor, Maintenance.
ease of recognition. Each character field is 20 characters long and accepts alpha-numeric data.
The inteIIiPANEL ™ control panel offers eight temperature inputs which can be programmed for thermocouple or RTD sensor types. Temperature inputs in the intelliPANEL ™ system are configured in groups of four. Thermocouple inputs can be configured as Type J, K, or E. RTD inputs can be configured as either 100 ohm Platinum 385, 100 ohm 392, or 1000 ohm. The inteIIiPANEL ™ system supports both Celsius and Fahrenheit temperature units along with up-scale or down- scale sensor burnout.
There are four programmable process interlocks with a text identification feature. The interlocks can be programmed for flow, pressure, time delay, or any variable required for your process.
All interlocks can be enabled or disabled and can be programmed for an open/closed logic state. Duty cycle, power in kilowatts, element resistance, time/ temperature, and ground fault monitor-
ing/trending values are also monitored.
intelliPANEL TM 3-Phase SCR Power Control Panel Specifications
Inputs: 4-Channel RTD Input Module
Touch Screen Display Screen Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.7 in. dia Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 x 240 Touch Grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 x 6 Communications Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ModBus Slave Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RS-422 4 Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RS-485 2 Wire Baud Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4, 4.8, 9.6, 19.2, 38.4 Kbaud Stop Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 or 2 Parity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Odd, Even, None On Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5, 10, 20 ms Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 to 128 Network Distance, Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,000 ft Number of Devices, Maximum . . . . . . . . . . . . . . . . . . . . . . . . . 32 per Network Baud Rate, Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30.4 Kbaud Driver Load, Maximum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 ohms Driver Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1.5 V Minimum No Load Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 mA Maximum Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 mA (62 ohms) Isolation Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . >1,014 ohms/7pF Voltage Withstand . . . . . . . . 1.2 kV rms per 1 second, 1.0 kV rms per 1 minute Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dipswitch Selectable Bias Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dipswitch Selectable RS-485/RS-422 Operation . . . . . . . . . . . . . . . . . . . . . . . . Dipswitch Selectable Connections . . . . . . . . . . . . . . Plug-In Removable Terminals for Field Termination PID Parameters Proportional Band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20˚ to 2,000˚ Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.6 to 60 Repeats per minute Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 to 99.99 seconds Reset Windup Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100% Fixed Rate Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X10 Fixed Manual Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0% to 100%, 1% Steps Control Set Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Full Range, 0.1˚ Setting Set Point Limits . . . . . . . . . . . . . . . . . . . . High and Low Full Range, 0.1˚ Setting Alarm Set Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Full Range, 1˚ Setting Alarm Dead Band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0˚ to 50.0 ∫ , 0.1˚ Setting Ramp to Set Point . . . . . . . . . . . . . . . . . . . . . 0˚ to 2,000˚ per Minute, 1˚ Setting Time Delay on Interlock . . . . . . . . . . . . . . 0 to 9,999 Seconds, 1 Second Settable Ground Fault Monitor Trip Setting Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 to 600 mA Current Indication . . . . . . . . . . . . . . . . . . . . . . . . 0% to 100% of Trip Set Point Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Levels Settable Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 hr clock, hr/min Format Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .m/d/yr Format Power Train Components Main Disconnect Switch . . . . . . . . . . . . . . . . Load Rated Shunt Trip with 25 kaic I ≤ T Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . >125% Load with 100 kaic Load Circuit Breakers . . . . . . . . . . . . . . . . . . . . >125% Load Rated with 25 kaic Contactors (If Supplied) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Load Rated Control and Alarm Control Modes Single Loop PlD Differential PID Cascade PlD/PlD
Type Pt100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . -200.0˚/850.0˚C (-328˚/1,562˚F) Type Pt1000 . . . . . . . . . . . . . . . . . . . . . . . . . . -200.0˚/595.0˚C. (-328˚/1,103˚F) Type jPt100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -38.0˚/450.0˚C. (-36˚/842˚F) RTD Excitation Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 µA Notch Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . >50 db Notches at 50/60 Hz Maximum Setting Time . . . . . . . . . . . . . . . . . . . 100 ms (Full-Scale Step Input) Common Mode Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 to 5 Vdc Absolute Maximum Ratings . . . . . . . . . . . . . Fault Protected Inputs to ±50 Vdc Sampling Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 rms per Channel Notes: 1. The three wires connecting the RTD to the module must be the same type and length. Do not use the shield or drain wire for the third connection. 2. Unused channels require shorting wires (jumpers) installed from terminals CH+ to CH- to COM to prevent possible noise from influencing active channels. 3. If an RTD sensor has four wires, the plus sense wire should be left unconnected. Number of Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4, Differential Common Mode Range . . . . . . . . . . . . . . . . . . . . . . . . . . . -1.3 Vdc to +3.8 Vdc Common Mode Rejection . . . . . . . . . . . . . . . . . . . 100dB min. at Vdc 50/60Hz. Input Impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5M Absolute Maximum Ratings . . . . . . . . . . . . . Fault-Protected Inputs to ±50 Vdc Update Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Channels per Scan Open Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . Upscale or Downscale Display Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±0.1˚C (±0.1˚F) Cold Junction Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Automatic Conversion Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 ms per Channel Warm-Up Time . . . . . . . . . . . . . . . . . . . 30 Minutes Typically ±1˚C Repeatability Linearity Error (End to End) . . . . . . . . . . . . . . . . ±1˚C Maximum, ±0.5˚C Typical Maximum Inaccuracy . . . . . . . . . . . . . . . ± 3˚C (Excluding Thermocouple Error) Linearity Error (All Input Ranges) . . . . . . . . . . . . . . . . . . . . 0.05% at 0˚ to 60˚C Typical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.03% at 25˚C Notes: 1. Shields should be grounded at the power source only. 2. All CH- terminals must be connected together. 3. Unused channels should have a shorting wire (jumper) installed from CH+ to CH-. 4-Channel Thermocouple Input Module Input Ranges Type J . . . . . . . . . . . . . . . . . . . . . . . -190˚ to 760˚C (-310˚ to 1,400˚F) Type E . . . . . . . . . . . . . . . . . . . . . . -210˚ to 1000˚C (-346˚ to 1,832˚F) Type K . . . . . . . . . . . . . . . . . . . . . . -150˚ to 1372˚C (-238˚ to 2,502˚F) Permissive Digital Inputs All . . . . . . . . . . . . . . . . . . Dry contact or triac rated for 120 Vac at 20 mA Relay Output Specifications Output Voltage Range . . . . . . . . . . . . . . . 6 to 240 Vac, 47 to 63Hz, 6 to 27 Vdc Maximum Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264 Vac, 30 Vdc Maximum Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2A per Point Maximum Leakage Current . . . . . . . . . . . . . . . . . . . . . . . . . 0.1 mA at 246 Vac Smallest Recommended Load . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 mA at 5 Vdc
Relay Operating Cycles Voltage and
Load Current
Type of Load 2 A 24 Vdc Resistive . . . . . . . . . . . . . . . . . . . . . . . . . 600 K . . . . . . . . . . . . 270 K 24 Vdc Solenoid . . . . . . . . . . . . . . . . . . . . . . . . . 150 K . . . . . . . . . . . . . 60 K 110 Vac Resistive . . . . . . . . . . . . . . . . . . . . . . . . 900 K . . . . . . . . . . . . 350 K 110 Vac Solenoid . . . . . . . . . . . . . . . . . . . . . . . . 350 K . . . . . . . . . . . . 150 K 220 Vac Resistive . . . . . . . . . . . . . . . . . . . . . . . . 600 K . . . . . . . . . . . . 250 K 220 Vac Solenoid . . . . . . . . . . . . . . . . . . . . . . . . 200 K . . . . . . . . . . . . 100 K 1 A
Ordering Information
Model inteIIiPANEL Series 1 IPZ2 Three Phase Two-Leg Zero-Fired SCR Power Control Panel Panel Configuration Real Time Process Indicators
Selectable Control Setups Single Loop, Delta "T"
Operational Features Global Alarm Display Alarm Setup, Mapping & Configuration, Interlock Status Display, Interlock Setup & Configuration, Real Time Trending (Six Pens), Heater Graphics, RS-485 MODBUS TM Communications, Eight Sensor Inputs Selectable in Groups of Four J, K. E Thermocouples or RTDs, Loop ID/Tagging, Hand/0ff/Auto Selection, Language Selection Option, Help Menu and Troubleshooting Pages, Security Code Protection, Ramp-to-Setpoint, Built-In Help and Troubleshooting Pages.
Heater Current, Line Voltage, Load Power Measurement (Kw/Kw/Hr), Duty Cycle (0%-100%), Ground Fault Leakage Trending, Life Factor Measurement, Resistance Monitoring, Inlet/Outlet/Shell
Cascade Outlet and Sheath Process and Sheath
Temperatures, Historical Hi/Low Temperature Indication & Record.
Remote 4-2OmA Command Signal
Code Current @ 40˚C (104˚F) Ambient
SCR Component
Max. # Circuits
Type 12 Enclosure Dimensions 4 , H x W x D, in. (mm)
02 03 06 08 10
100 Amp 150 Amp 200 Amp 300 Amp 400 Amp 550 Amp 650 Amp 800 Amp 1000 Amp 1200 Amp
MXPCII-4-02-1-1-L0-F01-0 MXPCII-4-04-1-1-L0-F01-0 MXPCII-4-06-1-1-L0-F02-0 MXPCII-4-08-1-1-L0-F03-0 MXPCII-4-10-1-1-L0-F04-0 MXPCII-4-12-1-1-L0-F05-0 MXPCII-4-14-1-1-L0-F06-0 2* MXPCII-4-10-1-1-L0-F04-0 2* MXPCII-4-12-1-1-L0-F05-0 2* MXPCII-4-14-1-1-L0-F06-0
4 4 4 4 4 8 8
72 x 36 x 12 (1828.8 x 914.40 x 304.8) 72 x 36 x 12 (1828.8 x 914.40 x 304.8) 72 x 36 x 12 (1828.8 x 914.40 x 304.8) 72 x 36 x 12 (1828.8 x 914.40 x 304.8) 72 x 36 x 12 (1828.8 x 914.40 x 304.8)
12 1 14 1 15 1 16 1 17 1
60.06 x 60.06 x 12.06 (1525.5 x 1525.5 x 306.3) 60.06 x 60.06 x 12.06 (1525.5 x 1525.5 x 306.3) 72.06 x 72.06 x 12.06 (1830.3 x 1830.3 x 306.3) 72.06 x 72.06 x 12.06 (1830.3 x 1830.3 x 306.3) 72.06 x 72.06 x 12.06 (1830.3 x 1830.3 x 306.3)
12 12 12
Code
Voltage 208 Vac 240 Vac 380 Vac 400 Vac 415 Vac
1 2 3 4 5 6
480 Vac Code Sensor Options J
(8) J Thermocouple Sensor Inputs (1-8) (8) K Thermocouple Sensor Inputs (1-8)
K
JK (4) J Thermocouple Sensor Inputs (1-4) and (4) K Thermocouple Sensor Inputs (5-8) KJ (4) K Thermocouple Sensor Inputs (1-4) and (4) J Thermocouple Sensor Inputs (5-8) R (8) RTD Sensor Inputs (1-8) RJ (4) RTD Sensor Inputs (1-4) and (4) J Thermocouple Sensor Inputs (5-8) RK (4) RTD Sensor Inputs (1-4) and (4) K Thermocouple Sensor Inputs (5-8) JR (4) J Thermocouple Sensor Inputs (1-4) and (4) RTD Sensor Inputs (5-8) KR (4) K Thermocouple Sensor Inputs (1-4) and (4) RTD Sensor Inputs (5-8) Code Overtemperature Controller Options 0 None 1 One Chromalox Model 1600-11130 1/16 DIN High Limit Controller (Sheath) 2 Two Chromalox Model 1600-11130 1/16 DIN High Limit Controllers (One Sheath. One Shell) 3 Two Chromalox Model 1600-11130 1/16 DIN High Limit Controllers (Two Sheath) 4 Three Chromalox Model 1600-11130 1/16 DIN High Limit Controllers (Two Sheath. One Shell) 5 Three Chromalox Model 1600-11130 1/16 DIN High Limit Controllers (Three Sheath) Code Communications Option 0 None 1 RS485 / 422 M0DBUS TM Code Remote On/Off Shutdown Contactor Option 0 None 1(*) Industrial 3-Pole Contactor 25 Amp Rating 5(*)
Industrial 3-Pole Contactor 60 Amp Rating Industrial 3-Pole Contactor 70 Amp Rating Industrial 3-Pole Contactor 80 Amp Rating Industrial 3-Pole Contactor 110 Amp Rating
2(*) 3(*) 4(*)
6(*) 7(*) 5(*)
Industrial 3-Pole Contactor 35 Amp Rating Industrial 3-Pole Contactor 40 Amp Rating Industrial 3-Pole Contactor 50 Amp Rating
Code Load Fusing Option (Thermal Magnetic Circuit Breakers) 9000 None 9025(*) 25 Amps per Circuit 9060(*) 60 Amps per Circuit 9030(*) 30 Amps per Circuit 9070(*) 70 Amps per Circuit 9035(*) 35 Amps per Circuit 9080(*) 80 Amps per Circuit 9040(*) 40 Amps per Circuit 9090(*) 90 Amps per Circuit 9045(*) 45 Amps per Circuit 9100(*) 100 Amps per Circuit 9050(*) 50 Amps per Circuit 9110(*) 110 Amps per Circuit
IPZ2 03
5
J
2 1
4(3)
9070(3)
Typical Model Number
Technical Notes: 1 Enclosure for codes 12, 14, 15, 16, and 17 are Floor-Mount Designs
2 Consult factory for 575 Vac Applications and Pricing 4 Ventilated NEMA 12 Enclosure Derates Enclosure to NEMA 1.
*Specify quantity of units.
3 Select Load Circuit Protection Option to be 125% Minimum of Actual Load Current
Ordering Information
Model inteIIiPANEL Series 1 IPZ3 Three Phase Three-Leg Zero-Fired SCR Power Control Panel Panel Configuration Real Time Process Indicators
Selectable Control Setups Single Loop, Delta "T"
Operational Features Global Alarm Display Alarm Setup, Mapping & Configuration, Interlock Status Display, Interlock Setup & Configuration, Real Time Trending (Six Pens), Heater Graphics, RS-485 MODBUS TM Communications, Eight Sensor Inputs Selectable in Groups of Four J, K. E Thermocouples or RTDs, Loop ID/Tagging, Hand/0ff/Auto Selection, Language Selection Option, Help Menu and Troubleshooting Pages, Security Code Protection, Ramp-to-Set point, Built-In Help and Troubleshooting Pages.
Heater Current, Line Voltage, Load Power Measurement (Kw/Kw/Hr), Duty Cycle (0%-100%), Ground Fault Leakage Trending, Life Factor Measurement, Resistance Monitoring, Inlet/Outlet/Shell
Cascade Outlet and Sheath Process and Sheath
Temperatures, Historical Hi/Low Temperature Indication & Record.
Remote 4-2OmA Command Signal
Code Current @ 40˚C (104˚F) Ambient
SCR Component
Max. # Circuits
Type 12 Enclosure Dimensions 4 , H x W x D, in. (mm)
02 03 06 08 10
100 Amp 150 Amp 200 Amp 300 Amp 400 Amp 550 Amp 650 Amp 800 Amp 1000 Amp 1200 Amp
MXPCIII-4-02-1-1-L0-F01-0 MXPCIII-4-04-1-1-L0-F01-0 MXPCIII-4-06-1-1-L0-F02-0 MXPCIII-4-08-1-1-L0-F03-0 MXPCIII-4-10-1-1-L0-F04-0 MXPCIII-4-12-1-1-L0-F05-0 MXPCIII-4-14-1-1-L0-F06-0 2* MXPCIII-4-10-1-1-L0-F04-0 2* MXPCIII-4-12-1-1-L0-F05-0 2* MXPCIII-4-14-1-1-L0-F06-0
4 4 4 4 4 8 8
60 x 48 x 12 (1524 x 1219.2 x 304.8) 60 x 48 x 12 (1524 x 1219.2 x 304.8) 60 x 48 x 12 (1524 x 1219.2 x 304.8) 60 x 48 x 12 (1524 x 1219.2 x 304.8) 60 x 48 x 12 (1524 x 1219.2 x 304.8)
12 1 14 1 15 1 16 1 17 1
77.06 x 60.06 x 12.06 (1830.3 x 1525.5 x 306.3) 77.06 x 60.06 x 12.06 (1830.3 x 1525.5 x 306.3) 84.12 x 112 x 14.12 (2136.6 x 2844.8 x 358.6) 84.12 x 112 x 14.12 (2136.6 x 2844.8 x 358.6) 84.12 x 112 x 14.12 (2136.6 x 2844.8 x 358.6)
12 12 12
Code
Voltage 208 Vac 240 Vac 380 Vac 400 Vac 415 Vac
1 2 3 4 5 6
480 Vac Code Sensor Options J
(8) J Thermocouple Sensor Inputs (1-8) (8) K Thermocouple Sensor Inputs (1-8)
K
JK (4) J Thermocouple Sensor Inputs (1-4) and (4) K Thermocouple Sensor Inputs (5-8) KJ (4) K Thermocouple Sensor Inputs (1-4) and (4) J Thermocouple Sensor Inputs (5-8) R (8) RTD Sensor Inputs (1-8) RJ (4) RTD Sensor Inputs (1-4) and (4) J Thermocouple Sensor Inputs (5-8) RK (4) RTD Sensor Inputs (1-4) and (4) K Thermocouple Sensor Inputs (5-8) JR (4) J Thermocouple Sensor Inputs (1-4) and (4) RTD Sensor Inputs (5-8) KR (4) K Thermocouple Sensor Inputs (1-4) and (4) RTD Sensor Inputs (5-8) Code Overtemperature Controller Options 0 None 1 One Chromalox Model 1600-11130 1/16 DIN High Limit Controller (Sheath) 2 Two Chromalox Model 1600-11130 1/16 DIN High Limit Controllers (One Sheath. One Shell) 3 Two Chromalox Model 1600-11130 1/16 DIN High Limit Controllers (Two Sheath) 4 Three Chromalox Model 1600-11130 1/16 DIN High Limit Controllers (Two Sheath. One Shell) 5 Three Chromalox Model 1600-11130 1/16 DIN High Limit Controllers (Three Sheath) Code Communications Option 0 None 1 RS485 / 422 M0DBUS TM Code Remote On/Off Shutdown Contactor Option 0 None 1(*) Industrial 3-Pole Contactor 25 Amp Rating 5(*)
Industrial 3-Pole Contactor 60 Amp Rating Industrial 3-Pole Contactor 70 Amp Rating Industrial 3-Pole Contactor 80 Amp Rating Industrial 3-Pole Contactor 110 Amp Rating
2(*) 3(*) 4(*)
6(*) 7(*) 5(*)
Industrial 3-Pole Contactor 35 Amp Rating Industrial 3-Pole Contactor 40 Amp Rating Industrial 3-Pole Contactor 50 Amp Rating
Code Load Fusing Option (Thermal Magnetic Circuit Breakers) 9000 None 9025(*) 25 Amps per Circuit 9060(*) 60 Amps per Circuit 9030(*) 30 Amps per Circuit 9070(*) 70 Amps per Circuit 9035(*) 35 Amps per Circuit 9080(*) 80 Amps per Circuit 9040(*) 40 Amps per Circuit 9090(*) 90 Amps per Circuit 9045(*) 45 Amps per Circuit 9100(*) 100 Amps per Circuit 9050(*) 50 Amps per Circuit 9110(*) 110 Amps per Circuit
IPZ3 03
5
J
2 1
4(3)
9070(3)
Typical Model Number
Technical Notes: 1 Enclosure for codes 12, 14, 15, 16, and 17 are Floor-Mount Designs
2 Consult factory for 575 Vac Applications and Pricing 4 Ventilated NEMA 12 Enclosure Derates Enclosure to NEMA 1.
*Specify quantity of units.
3 Select Load Circuit Protection Option to be 125% Minimum of Actual Load Current